Lithium Ion UPS Battery Versus VRLA Battery
           
  Units
Yuasa
Battery
NP 7-12
Gaia Lithium
Cells
UHP3414
ONCA
General Data
    7
Capacity 10H Rating
AH
7
7
Nominal Cell Voltage
Volt
2
3.6
Cell Weight
gram
440
320
Cell Volume
cu.cm
160
130
Total UPS Battery
Cells
240
133
UPS Battery weight
kg
106
55
UPS Battery Volume
Liters
38
22
Battery Voltage Maximum ( Float
Regime)
Volt
540
546
Battery Voltage Minimum
Volt
384
351
Discharge Current Maximim
Ampere
35
150
       
Backup Time
     
Discharge Time at 3C ( 21A)
minutes
5
18
Discharge Time at 2C ( 14A)
minutes
15
27
Discharge Time at 1C ( 7A)
minutes
40
54
Discharge Time at 0.3C (2A)
minutes
180
210
       
Temperature Dependance
     
Discharge capacity at -20 ºC
%
62
60
Discharge capacity at 0 ºC
%
85
90
Discharge capacity at + 20 ºC
%
100
100
Discharge capacity at +40 ºC
%
108
110
       
Cycles at 20 ºC to 80% Capacity  
     
Number of cycles to 100% discharge
Cycles
150
1000
Number of cycles to 50% discharge
Cycles
430
8000
Number of Cycles to 30% discharge
Cycles
1200
30000
       
Operating Temperature
     
Charging
ºC
-15 to + 50
-30 to + 60
Discharging
ºC
-15 to +60
-30 to + 60
Storage
ºC
-20 to +50
-40 to +60
       
Storage
     
Storage Time before charging
Months
6 to 9
6 to 12
Self discharge to 50%C at 20ºC
Months
17
10
Selfe discharge to 50%C at 40ºC
Months
5
5
       
Life Expectancy
     
Float regime at 20ºC to 80% Capacity
Years
3 to 5
9 to 10
Float regime at 30ºC to 80% Capacity
Years
1.5 to 2.5
4.5 to 5
Float regime at 40ºC to 80% Capacity
Years
0.75 to 1.25
2.25 to 2.5
       
* Weight and Volume of Li- Ion UPS battery includes 30% packing allowance.
Lithium Ion batteries are lately preferred over lead acid , based on longer lifetime, increased
backup time and environment friendliness. Until now Li Ion Batteries, although widely used
in portable electronics, didn't penetrate the UPS market due to flammability concerns. This
issue is now mitigated by introduction of internal battery protection circuits.  

The following table enables to compare the  performance of  a Three phase 480V 10kW
UPS  Lead Acid VRLA  battery bank with equivalent bank using Li Ion Cells.
For more insight and additional aspects  including Hazards and cost consideration see:
Pros and Cons of Li Ion UPS Batteries.